Global solar procurement from China — Get a Quote in 24h
Technical Guide

DC Surge Protection Devices for Solar PV Arrays

Published: September 23, 2026  |  9 min read  |  For EPC Engineers & Electrical Designers

Lightning and switching surges are among the leading causes of inverter damage, module bypass diode failure, and combiner box destruction in solar PV systems. A properly specified and installed DC surge protection device (SPD) is the first line of defense — yet SPD selection is frequently rushed during procurement, resulting in undersized devices that offer false security or oversized, expensive solutions. This guide walks through the IEC 61643-31 framework, selection methodology, sizing calculations, and installation requirements that every EPC engineer needs.

1. Why DC SPDs Are Essential in Solar PV Systems

Solar PV arrays are highly susceptible to both direct and induced lightning surges for several structural reasons. The array is installed outdoors, often on elevated ground or rooftops, presenting a large capture area. Long DC string cables running between the array and the inverter act as antennae, coupling induced overvoltage from nearby lightning strikes into the DC bus. Module bypass diodes and MOSFET-based MPPT stages in modern string inverters have very low overvoltage tolerance — typically just 1.5–2× nominal operating voltage before semiconductor junction breakdown.

IEC 62305-3 (protection of structures against lightning) mandates SPD installation at equipotential bonding points whenever lightning protection zones are established. IEC 60364-7-712 (electrical installations for solar photovoltaic power supply systems) requires DC SPDs wherever the DC cable run exceeds 10 m inside a building or where the risk assessment per IEC 62305-2 indicates their necessity. In practice, virtually all bankable commercial and utility-scale projects include DC SPDs as standard.

Insurance note: Many equipment warranties from Sungrow, Huawei, and SMA are voided by lightning damage when SPDs were absent or incorrectly sized. Always verify SPD specifications against inverter manufacturer requirements.

2. IEC 61643-31 Standard: The Governing Framework

IEC 61643-31 "Low-voltage surge protective devices — Part 31: Requirements and test methods for SPDs for use in photovoltaic installations" is the primary standard for DC SPDs in PV systems. It defines:

3. SPD Types: Type 1, Type 2, and Combinations

The IEC classification determines where in the system each SPD class is deployed:

Parameter Type 1 (Class I) Type 2 (Class II) Type 1+2 Combined
Test waveform10/350 µs (lightning)8/20 µs (induced)Both waveforms
Typical I_imp / I_n12.5–25 kA5–20 kA12.5 kA / 20 kA
Installation locationAt lightning protection zone boundary (LPZ 0→1)Inside building, sub-distribution (LPZ 1→2)Single device replaces Type 1 + Type 2 cascade
Typical PV applicationCombiner box at array field, direct lightning riskInverter DC input terminals, indoorCompact installations, small rooftop
TechnologySpark gap or combined MOV+spark gapMetal oxide varistor (MOV)Hybrid MOV + spark gap
Clamping voltage U_pTypically 4–8 kVTypically 2–4 kVTypically 2.5–4 kV
Cost relativeHighLow–mediumMedium–high
Required separation distance from Type 2N/A (if cascade used)Minimum 10 m cable or coordination inductorSingle device, no cascade needed

For most utility-scale and large C&I ground-mount projects, the standard approach is: Type 1+2 at each DC combiner box (installed at the array in the field), plus Type 2 at the inverter DC input. For rooftop systems where the DC cable run from array to inverter is short and indirect lightning risk is low, a Type 2 at the inverter DC input alone may suffice — subject to a lightning risk assessment per IEC 62305-2.

4. Sizing DC SPDs: Step-by-Step

Correct SPD sizing requires knowing four system parameters: maximum array Voc, string short-circuit current, system voltage class, and lightning protection zone designation. Follow this sequence:

Step 1: Determine Maximum Open-Circuit Voltage

Voc_max = Voc_STC × [1 + γ_Voc × (T_min − 25)] Example: 540 Wp module, Voc_STC = 49.5 V, γ_Voc = +0.28%/°C, T_min = −10°C Voc_max = 49.5 × [1 + 0.0028 × (−10 − 25)] = 49.5 × [1 + 0.0028 × (−35)] = 49.5 × 0.902 = 44.6 V per module For 20 modules in series: String Voc_max = 44.6 × 20 = 892 V DC

For a 1500 V DC system using 34 modules per string: Voc_max may reach 1400–1480 V DC. The SPD U_C rating must equal or exceed this value.

Step 2: Select U_C (Maximum Continuous Operating Voltage)

IEC 61643-31 requires: U_C ≥ 1.1 × Voc_max as an absolute minimum. Most designers use 1.2–1.25 × Voc_max to account for module positive power tolerance and measurement uncertainty. For a 1000 V DC system with Voc_max = 920 V: U_C ≥ 1,012 V → specify 1,100 V DC rated SPD. For 1500 V systems, specify 1,500 V or 1,800 V DC rated SPDs.

Step 3: Select I_imp / I_n Based on Lightning Risk Zone

The required impulse current is derived from the lightning protection level (LPL) per IEC 62305-1. For LPL III/IV (most commercial projects), I_imp = 12.5 kA per conductor is standard. For LPL I/II (high lightning incidence areas — tropical, mountainous), 25 kA per conductor. Type 2 I_n is typically 5–10 kA for building installations; 20 kA for direct array field deployment.

Step 4: Verify Protection Level U_p vs Equipment Withstand

The SPD clamping voltage U_p must be below the inverter's rated DC impulse withstand voltage. Most string inverters (Sungrow SG250HX, Huawei SUN2000, SMA Sunny Tripower X) specify 6 kV or 10 kV DC impulse withstand. Type 2 SPDs with U_p ≤ 4 kV are adequate. Where longer cable runs exist between SPD and inverter, add 1 kV per metre of cable (inductive voltage rise) to U_p when assessing protection adequacy.

5. Installation Requirements and Best Practices

Even a correctly specified SPD will fail to protect if installed incorrectly. Key installation rules per IEC 61643-31 and IEC 60364-7-712:

6. SPD Selection for 1500 V DC Systems

The industry's shift from 1000 V to 1500 V DC system voltage creates specific SPD challenges. At 1500 V, the arc extinction capability requirements are significantly higher — an SPD that fails short under 1500 V DC must interrupt a sustained arc against twice the voltage of a 1000 V system. Only SPDs explicitly rated and tested at 1500 V DC per IEC 61643-31 should be used. Verify that the manufacturer's datasheet clearly states the U_C rating (e.g., 1,500 V DC or 1,800 V DC), not just a nominal system voltage classification.

Leading SPD suppliers with verified 1500 V DC PV ratings include DEHN, Phoenix Contact, Citel, OBO Bettermann, and several Chinese manufacturers certified to IEC 61643-31. Econo Solar sources cost-effective IEC 61643-31 compliant DC SPDs for 1000 V and 1500 V systems alongside inverters and combiner boxes, simplifying procurement for EPC contractors.

7. Maintenance and Replacement Cycles

MOV-based SPDs have a finite energy absorption capacity. Each surge event partially degrades the MOV varistor material. Visual inspection alone is insufficient — a failed MOV may show no external signs. Best practices for SPD maintenance:

For EPC contractors and procurement teams sourcing SPDs alongside inverters, combiner boxes, and DC cables, Econo Solar offers bundled procurement from verified Chinese manufacturers with full IEC 61643-31 test certificates. Submit your bill of materials for a consolidated quote and lead-time confirmation.

Frequently Asked Questions

Do I need SPDs on both the positive and negative DC rails?

Yes. Surge currents can appear on either rail relative to earth, and a surge event between positive and negative poles is also possible. IEC 61643-31 defines test modes: CM (common mode, each pole to earth) and DM (differential mode, pole to pole). Full protection requires SPD elements covering both paths. For ungrounded (floating) 1500 V systems, symmetrical SPD topology with devices on both positive and negative rails to a mid-point reference is standard practice.

Can I use an AC SPD on the DC side of a PV system?

No. AC SPDs are designed and tested for AC current zero-crossing arc extinction. DC current has no natural zero crossing, making arc extinction much more difficult. An AC SPD used on DC may fail to extinguish an arc after a surge event, leading to sustained short-circuit current, fire, or explosion. Always use SPDs explicitly rated for DC operation per IEC 61643-31, with the DC voltage clearly stated on the device label and datasheet.

How do I know if my SPDs have been triggered by a surge?

Most Type 2 DC SPDs include a visual indicator window that changes color (typically green to red) when the internal MOV has degraded past its safe operating threshold. SPDs with remote signaling output provide a floating contact that changes state, which can be wired into the combiner box monitoring circuit or directly to the inverter's digital input. Monitoring platforms like Sungrow iSolarCloud and Huawei FusionSolar support SPD alarm status when wired accordingly. Do not rely on visual inspection alone for large arrays — implement remote status monitoring for all field-deployed SPD units.

Source Solar Equipment at Factory Prices

DC SPDs, combiner boxes, inverters, and cables — direct from China with IEC certifications and full logistics support.

Get a Free Quote in 24h