A standby generator without an automatic transfer switch is just an engine waiting for someone to throw a lever in the dark. The ATS detects mains failure, starts the genset, transfers the load, and reverses the whole sequence when the grid returns — and choosing the wrong type or rating is one of the most common (and expensive) mistakes in backup power projects.

What an ATS actually does

The transfer switch continuously monitors the utility supply. When voltage or frequency drifts outside limits for longer than a set delay (typically 3–5 seconds, to ride through flickers), it signals the generator to start, waits for stable genset output, then transfers the load. When mains power returns and holds stable (typically 5–30 minutes), it transfers back and lets the engine cool down before shutdown. Total time from blackout to generator power is normally 10–15 seconds for a standby-class installation.

The four transition types

TypeHow it worksBreak in supplyTypical use
Open transition (break-before-make)Disconnects one source before connecting the otherYes — milliseconds to secondsMost standby installations; simplest and cheapest
Delayed transitionOpen transition with a deliberate pause in neutral positionYes — 1–3 s programmedMotor-heavy loads; lets residual voltage decay before re-energising
Closed transition (make-before-break)Momentarily parallels genset with mains (≤100 ms overlap)NoHospitals, data centres, process loads; requires utility approval
Bypass-isolationAdds a manual bypass path around the ATSDepends on base typeCritical facilities that must maintain power during ATS servicing

Sizing the ATS: amperage

The ATS must be rated for the full load current of the circuit it protects — not the generator’s output. The calculation for a three-phase 400 V system:

I = kW × 1000 / (√3 × 400 × PF)

Example: a 200 kVA genset backing a 160 kW load at 0.8 PF draws about 289 A. The next standard ATS frame size up is 400 A — never size down, and allow 25% headroom for motor starting and future load growth. Common frame sizes run 63 / 100 / 160 / 250 / 400 / 630 / 800 / 1000 / 1250 / 1600 / 2000 / 3200 A.

3-pole or 4-pole?

Standards that matter

Installation notes from the field

Every Econo Solar genset from 5.5 to 4,000 kVA can ship with a factory-matched ATS panel and controller. Send us your load schedule and we’ll spec the switch with the genset.